co2-oil-level-control

Oil Level Infrared Sensors

sl-oil-level-sensors

Oil Level Infrared Sensors


The metallic oil level switch has been designed for use in level monitoring applications for the control of oil for compressors or liquid CO2 flow in transcritical or sub critical applications.
read more about metallic oil level infrared sensors

Oil Level Controls

sl-oil-level-controls

Oil Level Controls

The oil control optical level switches are designed for monitoring and controlling the oil level in compressor crank case, also available to directly fit CO2 Dorin compressors.
read more about oil level controls

K12 Oil Level Switch. Metallic IR sensor

K12 Oil Level Switch for refrigerant compressorsThe K12 family of optical level switches are specially designed for use in level monitoring for controlling the oil flow in screw compressors. They can be mounted directly on the crank case or the separator of screw compressors.
They have bodies made of stainless steel and sensor dome made of glass.
They are economical, dependable, and compact in size with overall dimensions of 105 x 36 mm and have no moving parts.
They are typically used for lubricating oil level monitoring, critical fluid level detection on machine tools, chillers and other OEM equipment, monitoring refrigerant liquid levels, etc.

These level switches use infrared technology for their operation. They consist of an infrared emitter and an optical receiver.
They have an operating temperature range of -40 to 125 deg C. There is a programmable timer inside these K12 optical level switches that allows a delay time to be set for delaying the output switching.
The output modes are normally closed in presence of liquids and open in air or vice versa. The AC output current is up to 200mA depending on model.

The K12 optical level switches must not be installed close to any infrared sources. The dome must be at least 50mm away from any reflective surface.
These level switches have electronic protection against transient over voltage.
The K12 family of optical level switches have a detection accuracy of +/- 2 mm. They can withstand maximum pressure of 30 bars.
Click here to download a PDF short technical data sheet (90.42 Kb) Click here to download a PDF technical sheet (470.53 Kb)

Technical Data of the Instrument

Operation mode : Detect liquid presence with contact
Repeatability : ± 2 mm
Body materials : Stainless Steel
Sensible dome : Glass
Electronic protections : Transient over voltage
Max. temperature range : From –40ºC up to +125ºC
Storage temperature : From –40ºC up to +125ºC
Supply voltage : 90 - 230 VAC 50/60 Hz
AC Output current : up to 200 mA Max
Output mode : Output Normally Open or Closed in the air
Delay times : Customizables depending on application needings
Max pressure : up to 30 bar
Torque tighten : 40 Ntm

Electrical Connection

k12-electrical-connection

Mechanical Dimensions

k12-mechanical-dimensions

 